Pin Types

Standard ANSI Standard Designs

 

Victor manufacturers three classes of pin type insulators. Low voltage pin types are manufactured and tested to the requirements of ANSI Standard C29.5, high voltage pin types to ANSI Standard C29.6, and special designs for use in areas of high contamination.

All Victor Pin Types are RUS accepted where a specific RUS classification exists.

Standard color is sky gray, with chocolate or white available upon request. Standard products are radio free treatment (exception Cat. No. 35 fog bowl).

Low Voltage Pin Types (ANSI Class 55-2 – Class 55-6)

These insulators are all single piece designs with porcelain threads, a design which years of field experience has proven to be the best. Victor Insulators lead the way in developing and introducing this design concept to the marketplace.

USA Cat. No. Import Cat. No. ANSI Class App. kV* RUS Accepted Neck Type Pin Hole Diameter (in.) Qty per Pallet
8R VI 608R 55-2 7.2 Yes C 1 960
5R VI 605R 55-3 11.5 Yes C 1 810
6R VI 606R 55-4 13.2 Yes F 1 324
9R VI 609R 55-5 14.4 F 1 288
11R VI 611R 55-6 23 J 1 144
* Typical application voltages are intended as a guide only and may be affected by service environment or other factors. Please consult factory if more information is required.

Catalog numbers with suffix R are radio freed. For non radio freed (plain) insulators omit the suffix R from the catalog number.

High Voltage Pin Types (ANSI Class 56-1 – 56-4)

USA Cat. No. Import Cat. No. ANSI Class App. kV* RUS Accepted Neck Type Pin Hole Diameter (in.) Qty per Pallet
27R VI 627R 56-1 14.4/23 Yes J 1-3/8 288
133R VI 633R 56-2 23 K 1-3/8 112
145R VI 645R 56-3 34/5 Yes K 1-3/8 80
255R VI 655R 56-4 46 Yes 1-3/8 27

High Leakage and Fog Bowl Pin Types (Special Designs)

These insulators have been designed by Victor to meet specific customer application needs in areas of extreme service conditions due to contamination. Fog Bowl designs offer high protected leakage areas.

While no ANSI Standards exist for these products Victor manufactures and tests each of these insulators to meet the general requirements of ANSI Standards C29.1 and C29.5 to ensure quality and a lifetime of trouble free service.

Due to the unusual service conditions that these insulators experience, typical application voltages are not given. The factory should be consulted to determine the appropriate insulator for use in a given application.

All insulators are designed with standard neck dimensions so that pre formed (wrap lock) ties may be used.

USA Cat. No. Type Leakage Distance (in.) 60 Hz Dry Flashover (kV) Neck Type Pin Hole Diameter (in.) Qty per Pallet
33R High Leakage 13 85 F 1 240
34R High Leakage 13 85 F 1-2/8 240
35 Fog Bowl 11 65 C 1 216
39R Fog Bowl 16.5 100 F 1 150
40R Fog Bowl 16.5 100 F 1-3/8 150
41R Fog Bowl 21.5 110 J 1 150
42R Fog Bowl 21.5 110 J 1-3/8 150

Mounting Studs

Mounting studs are available at an additional cost. Victor Insulators ‘ studs can be used with all other manufacturers’ line posts that meet ANSI standards.
Cat. No. Crossarm Type Line Post Ratings kV Shipping Weight Each,Pounds Dimensions (in)
72087 Wood 34.5- 69 7 x 4 x ¾ 1.50
72088 Steel 34.5- 69 1¾ x 1 9/16 x ¾ 0.56
72090 Steel 13.2- 23 1¾ x 1 9/16 x 5/8 .4 5
72091 Wood 13.2- 23 7 x 4 x 5/8 1 .25

Clamps

CLAMPS Victor Insulators yoke design will accept other manufacturers’ clamps with a standard nominal 4″ trunnion. Conductor clamps have been designed with reversible keepers, so that three designs of clamps will accommodate conductors ranging from .25″ to 1.5″ in diameter. Victor Insulators’ clamps will fit any 4″ spaced yoke of either vertical or horizontal design.

Category Number Conductor Size (in) Dimensions (in) Shipping Weight, each (lbs)
Min. Max. Length Width
72157 0.25 0.562 3 7/8 0.87
72158 0.50 1.062 5¼ 3 7/8 0.99
72159 1.00 1.500 3 7/8 1 .25